HMI Router Counters

The System Sentry provides counters to monitor CIMPLICITY router performance.

Accumulated totals since the project started

For Counter Counts the Number of:
A Messages Sent Messages sent by the router.
A Messages Rec Messages received by the router.
A RCM Requests Connection management requests. When a viewer needs to attach to a project, it makes an RCM request.
N Socket Errors TCP/IP sockets are used to communicate. For example, if a cable is accidentally pulled off a socket, an error will be counted. Typically, there should not be many socket errors.

Indicators of current performance

For Counter Displays the
N Messages Sent/sec Messages sent by the router per second.
N Messages Rec/sec Messages received by the router per second.
N Sockets Sockets that are currently in use by the router. The router opens a socket for each connection to each computer. The router also uses sockets for other reasons. Example The router creates a separate connection between redundant nodes beyond the router message queue connection to show if the element has gone away. That can add extra sockets.
N Socket Errors/sec Socket errors per second show if there currently is a problem. For example, a cable needs to be tightened.
N Connected Nodes Nodes that are connected to the selected node.
E Ports Application ports in use by the router. This may be a well-known or anonymous port that is being sent out to a process. This indicates the current level of use.
E RR Outstanding Response required messages from a process that are on the router's queue waiting to be received by another process. If the router knows that the receiving process is unavailable, it informs the originating process.

Expertise Code

N Novice
A Advanced
E Expert