POLL_AFTER_SET
Point Type | Device | |
Maximum Field Length | Boolean | |
CIMPLICITY Field Name | Poll After Set | |
Description | Determines if polling should be done after a setpoint. | |
Values | Valid values are: | |
0 | Do not poll (default) | |
1 | Scan immediately |
These devices include:
- AB Ethernet
- Mitsubishi TCP/IP
- Sharp
- Triplex
For these interfaces, if the device response to a poll request is received during the poll after set processing, the response on the poll after set can be processed first.
- Do the following if either condition occurs.
- This behavior is observed and is a problem for the application
- Normal polling delivers the data to the application in a time frame sufficient to meet the application needs.
Clear the Poll after Set checkbox on the Device tab of the Point Properties dialog box.
- If a poll after set is required, the asynchronous polling can be disabled on the port.
To disable the asynchronous polling, define the global parameter <PORT>_SYNC_ONLY .
Synchronous polling is disabled by default.