Recommended Configuration for RX7i Devices
Procedure
- Open the Triplex project in Workbench and, from the Tools menu, select Command Prompt.
- Type "idtpop device" and press Enter.
- Open the device.idt file in a text editor. The device.idt file is located in the project folder (e.g. C:\Program Files\Proficy\Proficy CIMPLICITY\MyTriplexProject).
- For the device in question, change the dead_scan_rate from 45 to a smaller number, such as 10, and save the file.
- In the Command Prompt window, type "scpop device" and press Enter.
- In Workbench, from the Project menu, select Configuration Update. A message appears asking to copy the master configuration data to run-time data.
-
Click OK.
When you start the project, it should recover 20 to 30 seconds after a failover/recovery.