Modify log_names.cfg
About this task
The Marquee Driver uses an IPC datagram queue to receive alarm messages. The default size for this queue is 10. This default is acceptable for bursts of 50 alarms during testing, however system loading will change performance.
If you find an IPC datagram queue overflow message in the Status Log for a Marquee Driver process, you can increase the size of the IPC queue.