DX9100 I/O Map

The following table shows the valid range of record numbers in each of the DX9100 regions. Depending on the configuration of extension modules installed in the DX9100, not all records may be available in any particular device.

Region Valid Range Notes
AI 1–72 Read only
BI 1–72 Read only
AO 1–72 Setpoint sets hold bit.
BO 1–72 Setpoint sets hold bit.
ADF 1–8
ADI 1–72
BD 1–32
LRS 1–64 Read only
PMK 1–240 These values are stored in EEPROM. They are writable but setpoint should be limited in frequency.
PMO 1–96
PML 1–96
PMA 1–96