Configuring Fault Points for IC660BBA100 Blocks
For the 115 VAC 4 In/2 Out Analog Block - Phase B (IC660BBA100), configure points %GD0 through %GD6 , where:
- %GD0 is the Block-Level diagnostic point.
- %GD1 through %GD4 are the Circuit-Level diagnostic points for inputs.
- %GD5 through %GD6 are the Circuit-Level diagnostic points for outputs.
All diagnostic points are Analog device points with a Point Type of USINT. The Update Criteria is On Change for the Block-Level diagnostic point and Unsolicited for the Circuit-Level diagnostic points.
Prior to receiving fault data from the block, you must enable outputs to it.