Data Loader

About the Calibration Data Loader

Using the Calibration Data Loader, you can implement Calibration Management when you have calibration data in a legacy system, which is not supported by GE Digital APM. To import data using the Calibration Data Loader, GE Digital APM provides an Excel template, Calibration_DataLoader.xlsx, which supports baseline Calibration Management in GE Digital APM. You must export your legacy system so that the data can be used to populate the template. The data from the template will then be imported into GE Digital APM using the Calibration Data Loader.

Note: The Excel template is referred to throughout this documentation as the data loader workbook.

The data loader workbook can be used in the following scenarios:

  • Loading existing legacy calibration data into GE Digital APM so that you can retain visibility into previous calibration results, compare the results with current and future results, and generate graphs and reports.
  • Loading calibration data from a documenting process calibrator that is not supported by GE Digital APM.

After importing the data, the Calibration Data Loader creates the following records in GE Digital APM:

  • Test Equipment
  • Test Equipment Detail
  • Standard Gas Cylinder
  • Standard Gas Components
  • Calibration Profile
  • Calibration Template, Analog
  • Calibration Template, Discrete
  • Calibration Template, Single Component Analyzer
  • Calibration Template, Multi-Component Analyzer
  • Calibration Template Detail, Analyzer
  • Calibration Task
  • Calibration, Analog
  • Calibration, Discrete
  • Calibration, Single Component Analyzer
  • Calibration, Multi-Component Analyzer
  • Calibration Result
  • Calibration Recommendation

About the Calibration Data Loader Requirements

Before importing data using the data loader workbook, you must have completed the following steps:

  • Deploy the Calibration Management module.
  • Populate the Equipment, Functional Location, or custom asset to establish relationship with the families in Calibration Management.
  • Enter a valid Asset ID into the data loader workbook. To do this, the Equipment, Functional Location, or custom asset must exist in the GE Digital APM database.
  • By default, the Standard Gas Cylinder family is not linked to any other family (except Standard Gas Component) used in Calibration Management. If you want to create Standard Gas Cylinder and Standard Gas Component records using the Data Loader, and link them to Equipment, Functional Location, or custom asset, then you must define the relationship using the Has Standard Gas relationship family by creating the following relationship definition:
    • Predecessor: Equipment, Functional Location, or custom asset
    • Predecessor Cardinality: Zero or many
    • Successor: Standard Gas Cylinder
    • Successor Cardinality: Zero or Many
  • The Security User performing the data load operation must be associated with either the MI Data Loader User or MI Data Loader Admin Security Role.

About the Calibration Data Loader Data Model

The Calibration Data Loader does not load the entire data model illustrated in the normal help documentation. The following data model illustrates the records that the Data Loader supports. Equipment, Functional Location, or custom asset records, illustrated in green, must exist prior to importing data.

Note: In the diagram, boxes represent entity families and arrows represent relationship families that are configured in the baseline database. You can determine the direction of each relationship definition from the direction of the arrow head: the box from which the arrow originates is the predecessor, and the box to which the arrow head points is the successor.

About the Calibration Data Loader General Loading Strategy

The imported data must load in a specific sequence in order to successfully populate fields, to create records, and to link them to the predecessor and/or successor records.

Best Practices

When importing data using the data loader workbook, you must use the following best practices:

  • ID fields (Row 2 of each worksheet) must not include special characters (other than underscores) or spaces.
  • Columns (including columns representing custom fields) in the worksheets should be formatted as Text.
  • You should not try to create and update a component in the same data loader workbook.
  • You must consider the rules described in the Workbook Layout and Use section of this document while using the Calibration Data Loader.

Load Sequence

The data load is performed in the following sequence:

  1. The Batch worksheet is processed. All the records that contain the same batch number are uploaded together.
  2. The Test Equipment worksheet is processed. The Data Loader searches for the record that you have specified in the Equipment ID column. If the record exists, it is updated. Otherwise, a Test Equipment is created.
  3. The Test Equipment History worksheet is processed. If a Test Equipment History record exists for the Test Equipment specified in the Parent ID column, it is deleted, and a new Test Equipment History record is created based on the details you provide in this worksheet.
  4. The Standard Gas Cylinder worksheet is processed. The Data Loader searches for the record that you have specified in the Standard Gas Cylinder ID column. If the record exists, it is updated. Otherwise, a Standard Gas Cylinder is created.
  5. The Standard Gas Component worksheet is processed. If a Standard Gas Component record exists for the Standard Gas Cylinder specified in the Parent Key column, it is deleted, and a new Standard Gas Component record is created based on the details you provide in this worksheet.
  6. The Profile Template worksheet is processed. The Data Loader searches for the record that you have specified in the Template ID column. If the record exists, it is updated. Otherwise, depending on the value in the Calibration Type column, one of the following records is created:
    • Calibration Template, Analog
    • Calibration Template, Discrete
    • Calibration Template, Single Component Analyzer
    • Calibration Template, Multi-Component Analyzer
  7. The Calibration Profile worksheet is processed. The Data Loader searches for the record that you have specified in the Profile ID column. If the record exists, it is updated. Otherwise, a Calibration Profile is created and linked to the template that you have specified in the Profile Template column.
  8. The Analog Template, Discrete Template, Single Component Template, and Multi Component Template worksheets are processed. The Data Loader searches for the records that you have specified in the Template ID column. If the records exist, they are updated. Otherwise, the following records are created:
    • Calibration Template, Analog
    • Calibration Template, Discrete
    • Calibration Template, Single Component Analyzer
    • Calibration Template, Multi-Component Analyzer

    These records are linked to the profile and Equipment, Functional Location, or custom asset you have specified in the Profile ID and Asset ID columns respectively.

  9. The Single Comp Temp Detail worksheet is processed. If a Calibration Template Detail, Analyzer record exists for the template specified in the Template Parent ID column, it is updated. Otherwise, it is created and linked to the Calibration Template, Single Component Analyzer record that you have specified in the Template Parent ID column.
  10. The Calibration Task worksheet is processed. The Data Loader searches for the record that you have specified in the Task ID column. If the record exists, it is updated. Otherwise, a Calibration Task is created and linked to the Equipment, Functional Location, or custom asset that you have specified in the Asset ID column and the Calibration Template that you have specified in the Calibration Template ID column.
  11. The Calibration Event worksheet is processed. The Data Loader searches for the record that you have specified in the Event ID column. If the record exists, it is updated. Otherwise, one of the following records is created for each row:
    • Calibration, Analog
    • Calibration, Discrete
    • Calibration, Single Component Analyzer
    • Calibration, Multi-Component Analyzer

    The record is linked to the Equipment, Functional Location, or custom asset and Test Equipment that you have specified in the Asset ID, Test Equipment ID No 1, Test Equipment ID No 2, and Test Equipment ID No 3 columns respectively.

  12. The Calibration Result worksheet is processed. For the Calibration record specified in the Event ID column, if a Calibration Results record exists with the sequence:
    • If the value in the Calibration Results Family ID column is MI_CRAN0000, and the Calibration Results, Analog record that you have specified in the Event ID and Calibration Sequence Number columns exists, then the Calibration Results, Analog record is updated. Otherwise, it is created and linked to the Calibration, Analog record that you have specified in the Parent Key (Analog) column.
    • If the value in the Calibration Results Family ID column is MI_CRDS0000, and the Calibration Result, Discrete record that you have specified in the Event ID and Calibration Sequence Number columns exists, then the Calibration Result, Discrete record is updated. Otherwise, it is created and linked to the Calibration, Discrete record that you have specified in the Parent Key (Discrete) column.
    • If the value in the Calibration Results Family ID column is MI_CRANZR00, and the Calibration Results, Analyzer record that you have specified in the Event ID and Calibration Sequence Number columns exists, then the Calibration Results, Analyzer record is updated. Otherwise, it is created and linked to the Calibration, Analyzer Single Component or the Calibration, Analyzer Multi-Component record that you have specified in the Parent Key(Single/Multi Component) column.
  13. The Calibration Recommendation worksheet is processed. The Data Loader searches for the record that you have specified in the Recommendation ID column. If the record exists, it is updated. Otherwise, it is created and linked to the Equipment, Functional Location, or custom asset and Calibration records that you have specified in the Asset ID and Event ID columns respectively.

About the Calibration Data Loader Workbook Layout and Use

To import data using the Calibration Data Loader, GE Digital APM provides the data loader workbook (Calibration_DataLoader.xlsx) that supports baseline Calibration Management in GE Digital APM. You must use this workbook to import data. You can modify the workbook to include custom fields used by your organization.

The following table provides a list of the worksheets that are included in the data loader workbook.

WorksheetDescription
BatchThis worksheet is used to define the batches. Data is imported in batches. All the records that are assigned a particular batch number will be imported together. If a record in a batch is not imported, then none of the records in the batch are imported.
Test Equipment

This worksheet is used to create or update Test Equipment records.

Test Equipment History

This worksheet is used to create Test Equipment History records. If a Test Equipment History record with the same ID exists, it is deleted, and a new one is created based on the values you enter in this worksheet.

Standard Gas CylinderThis worksheet is used to create or update Standard Gas Cylinder records.
Standard Gas ComponentThis worksheet is used to create Standard Gas Component records. If a Standard Gas Component record with the same ID exists, it is deleted, and a new one is created based on the values you enter in this worksheet.
Profile Template

This worksheet is used to create or update Calibration Profile Templates records.

Calibration Profile

This worksheet is used to create or update Calibration Profile records.

Analog Template

This worksheet is used to create or update Calibration Template, Analog records.

Discrete TemplateThis worksheet is used to create or update Calibration Template, Discrete records.
Single Component TemplateThis worksheet is used to create or update Calibration Template, Single Component Analyzer records.
Multi Component TemplateThis worksheet is used to create or update Calibration Template, Multi-Component Analyzer records.
Single Comp Temp DetailThis worksheet is used to create or update Calibration Template Detail, Analyzer records.
Note: You can use the same worksheet to create or update Calibration Template Detail, Analyzer records for a profile template or an applied template.
Calibration TaskThis worksheet is used to create or update Calibration Task records.
Calibration EventThis worksheet is used to create or update the following records:
  • Calibration, Analog
  • Calibration, Discrete
  • Calibration, Single Component Analyzer
  • Calibration, Multi-Component Analyzer
Calibration ResultFor manual calibration, this worksheet is used to create or update the following records:
  • Calibration Results, Analog
  • Calibration Result, Discrete
  • Calibration Results, Analyzer

You cannot, however, create or update the aforementioned records for an automated calibration.

Calibration Recommendation This worksheet is used to create or update Calibration Recommendation records.
(Picklist)This worksheet provides a list of valid values available for fields that have pick lists. When you load data using the data loader, the data in this worksheet is not loaded.

Color Coding

Certain columns on the worksheets have different functions and requirements. To illustrate this, certain columns are color-coded. The following table lists the colors and what they represent.

Color

Description

Comments

Required Key Fields

Indicates columns that contain values that are used by the Data Loader to look up and create records. If these columns are removed from the worksheets, the data load will fail. While the worksheets require that these columns be present, values are not necessarily required in these columns.

Fields Required for CalculationIndicates columns that contain values that are required to perform calculations. Some cells only require values in certain cases. Such cases are found in parentheses in the first row of each worksheet.
Recommended FieldsIndicates columns that are recommended to contain values.
Custom FieldsIndicates columns where you can specify custom fields.

Limitations

The Calibration Data Loader has the following limitations:

  • You must use the data loader workbook. If you modify the format of the values in columns in any of the worksheets, you will not be able to import data.
  • The values that you enter in the data loader workbook are case-sensitive.
  • If you reimport data, the records that have been created by the Calibration Data Loader will be updated. Therefore, while reimporting data, if you remove the data for a field in the data loader workbook, the value for the corresponding field in GE Digital APM will be blank.

Batch

This worksheet is used to define batches.

Field Caption

Field ID

Data Type (Length)

Comments

BATCH_ID

BATCH_ID

Numeric

A value is required and must be unique. Enter a batch number. Data related to all the rows that contain the same batch number in the remaining worksheets is imported in a single batch.

Test Equipment Worksheet

The Test Equipment worksheet stores the details of the Test Equipment records.

Field Caption

Field ID

Data Type (Length)

Comments

BATCH_ID

BATCH_ID

Numeric

A value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.

Equipment ID

MI_TESTEQUIP_EQUIP_ID_C

Character (50)

A value is required and must be unique. This value identifies the Test Equipment.

Serial Number

MI_TESTEQUIP_SN_C

Numeric

A value is required.

Certification Interval

MI_TESTEQUIP_CERT_INTV_N

Numeric

A value is required.

Certification Units

MI_TESTEQUIP_CERT_UNITS_C

Character (50)

A value is required.

This column may only contain one of the System Code IDs in the MI_TIME_UNITS System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Model Number

MI_TESTEQUIP_MOD_NO_C

Character (50)

A value is required.

Manufacturer

MI_TESTEQUIP_MFR_C

Character (50)

A value is required.

Last Certification Date

MI_TESTEQUIP_CERT_DATE_D

Date

A value is required. Enter the value in the following format: YYYY-MM-DD HH:mm:ss

Site Reference Name MI_SITE_NAMECharacter (255)
Important: Site Reference records must preexist in GE Digital APM. The data loader does not create Site Reference records, but simply provides foreign key data in the asset records, as determined in the source workbook. If the site reference record does not preexist, then you will receive an error.
  • Enter the site name to designate which site the Test Equipment or Standard Gas Cylinder record, once loaded into GE Digital APM, will be filtered by.

    -or-

  • Enter *Global* to indicate a that the site reference should be left global. Meaning that it will not be filtered by site in GE Digital APM.
Note: Only super users are permitted to update Site Reference records.

Assigned To

MI_TESTEQUIP_ASSIGNED_TO_C

Character (50)

None

Category

MI_TESTEQUIP_SAP_CATEG_C

Character (50)

None

Certification Supplier is ISO/IEC 17025 Centified

MI_TESTEQUIP_CERT_SUPP_CERT_C

Character (5)

None

Class

MI_TESTEQUIP_SAP_CLASS_C

Character (50)

None

NIST Traceability Required

MI_TESTEQUIP_NIST_REQD_C

Character (5)

None

Purchase Date

MI_TESTEQUIP_PRCH_D

Date

Enter a value in the following format: YYYY-MM-DD HH:mm:ss

Purchase Order Number

MI_TESTEQUIP_PO_NO_C

Character (50)

None

Type

MI_TESTEQUIP_OBJ_TYP_C

Character (50)

None

Last Check Date

MI_TESTEQUIP_LST_CHK_DATE_D

Date

Enter the value in the following format: YYYY-MM-DD HH:mm:ss

Check Interval

MI_TESTEQUIP_CHECK_INTV_N

Numeric

None

Check Interval Units

MI_TESTEQUIP_CHK_INTV_UNITS_C

Character (50)

This field is required only if the Check Interval field contains a value.

This column may only contain one of the System Code IDs in the MI_TIME_UNITS System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Description

MI_TESTEQUIP_DESCR_C

Character (255)

None

Vendor

MI_TESTEQUIP_EQUIP_VNDR_C

Character (50)

None

Maintenance Plant

MI_TESTEQUIP_MAINT_PLANT_C

Character (50)

None

Test Equipment History Worksheet

The Test Equipment History worksheet stores the details of the Test Equipment History records.

Field CaptionField IDData Type (Length)Comments
BATCH_IDBATCH_IDNumericA value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.
Parent IDMI_TST_EQUIP_HIST_PARE_KEY_NCharacter (50)A value is required. This cell may only contain a value that exists in the list in the Test Equipment ID field for Test Equipment records.
Certification DateMI_TST_EQUIP_HIST_CERT_DT_DDateA value is required. Enter the value in the following format: YYYY-MM-DD HH:mm:ss
Certification NumberMI_TST_EQUIP_HIST_CERT_NUM_CCharacter (50)A value is required.
SupplierMI_TST_EQUIP_HIST_SUPPL_CCharacterA value is required.
Entered ByMI_TST_EQUIP_HIST_ENT_BY_CCharacter (50)A value is required.
Date CreatedMI_TST_EQUIP_HIST_DATE_CDateEnter a value in the following format: YYYY-MM-DD HH:mm:ss

Standard Gas Cylinder Worksheet

The Standard Gas Cylinder worksheet stores the details of the Standard Gas Cylinder records.

Field Caption

Field ID

Data Type (Length)

Comments

BATCH_ID

BATCH_ID

Numeric

A value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.

Standard Gas Cylinder IDMI_SG000000_CYL_IDCharacter (50)A value is required.
Site Reference NameMI_SITE_NAMECharacter (50)A value is required.
Standard Gas Cylinder DescriptionMI_SG000000_CYL_DESCR_CCharacter (255)None
Minimum Cylinder PressureMI_SGCY0000_MIN_CYL_PRES_NNumericNone
Actual Sample VolumeMI_SGCY0000_SMPL_VOL_NNumericNone
Laboratory Analysis NumberMI_SGCY0000_LAB_NBR_CCharacter (50)None
Cylinder Connection NumberMI_SGCY0000_CYL_CONN_CCharacter (25)This column may only contain one of the System Code IDs in the MI GAS CYLINDER CONNECTION NUMBER System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.
Cylinder TypeMI_SGCY0000_CYL_TYP_CCharacter (50)This column may only contain one of the System Code IDs in the MI GAS CYLINDER TYPE System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.
Cylinder ManufacturerMI_SGCY0000_CYL_MFR_CCharacter (50)None
Cylinder SizeMI_SGCY0000_CYL_SZ_CCharacter (25)This column may only contain one of the System Code IDs in the MI GAS CYLINDER SIZE System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.
Expiration DateMI_SGCY0000_CYL_EXP_DDateEnter a value in the following format: YYYY-MM-DD HH:mm:ss
In Service DateMI_SGCY0000_CYL_IN_SRVC_DDateEnter a value in the following format: YYYY-MM-DD HH:mm:ss
Cylinder OwnerMI_SGCY0000_CYL_OWNR_CCharacter (50)None

Standard Gas Component Worksheet

The Standard Gas Component worksheet stores details of Standard Gas Components.

Field Caption

Field ID

Data Type (Length)

Comments

BATCH_ID

BATCH_ID

Numeric

A value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.

Standard Component NameMI_SGCM0000_CMPNT_NM_CCharacter (50)A value is required.

This column may only contain one of the System Code IDs in the MI CHEMICAL COMPONENTS System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Standard Analytical ResultMI_SGCM0000_ANLYTCL_RSLT_NNumericA value is required.
Standard Component UOMMI_SGCM0000_CMPNT_UOM_CCharacter (15)A value is required.

This column may only contain one of the System Code IDs in the UOME System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Parent KeyMI_SGCM0000_PARE_KEY_NNumericA value is required. Enter the ID of the Standard Gas Cylinder. It will be converted to the parent key when you import data.
Standard Gas Cylinder DescriptionMI_SG000000_CYL_DESCR_CCharacter (255)None
Standard Blend ToleranceMI_SGCM0000_BLND_TOL_NNumericNone
Standard Requested ValueMI_SGCM0000_REQ_VAL_NNumericNone
Standard Gas Cylinder IDMI_SG000000_CYL_IDCharacter (50)Enter the ID of the Standard Gas Cylinder.
Standard Balance ContentMI_SGCM0000_BLNC_CNTNT_LBooleanEnter True or False.

Profile Template Worksheet

The Profile Template worksheet stores the details of the Calibration Profile Template records.

Field Caption

Field ID

Data Type (Length)

Comments

BATCH_ID

BATCH_ID

Numeric

A value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.

Template ID

MI_TM000000_ID

Character (255)

A value is required and must be unique. This value identifies the Template.

Calibration Family IDFamily_IDCharacter (50)A value is required. Enter one of the following values based on the calibration type:
MI_TMCASCANCalibration TypeCalibration Family ID
AnalogMI_TMCAAN00
DiscreteMI_TMCADSCT
Single component analyzer
Multi-component analyzerMI_TMCAMCAN
Calibration Type MI_TMCA0000_CAL_TYP_CCharacter (50)

A value is required.

This column may only contain one of the System Code IDs in the MI_CALIBRATION_TYPE System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Error AssesmentMI_TMCA0000_ERR_ASSES_CCharacter (50)

A value is required in the Calibration Template, Analog records, Calibration Template, Discrete, and Calibration Template, Single Component Analyzer records.

This column may only contain one of the System Code IDs in the CALIBRATION_ERROR_ASSESSMENT System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Input Type

MI_TMCA0000_INPUT_TYP_C

Character (50)

A value is required.

This column may only contain one of the System Code IDs in the MI_CALIBRATION_IO_TYPES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Output Type

MI_TMCA0000_OUTPU_TYP_C

Character (50)

A value is required.

This column may only contain one of the System Code IDs in the MI_CALIBRATION_IO_TYPES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Max Error Limit

MI_TMCA0000_ERR_LIM_N

Numeric

A value is required.

Primary Input LRVMI_TMCA0000_PRI_IN_LRV_NNumericA value is required.
Primary Input URVMI_TMCA0000_PRI_IN_URV_NNumericA value is required.

Primary Input Range Units

MI_TMCA0000_PRI_IN_RV_UOM_C

Character (10)

A value is required. Depending on the value in the Calibration Type field, this field contains one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST

Primary Output LRV (Analog)

MI_TMCA0000_PRI_OUT_LRV_N

Numeric

A value is required for analog calibration.

Primary Output URV (Analog)

MI_TMCA0000_PRI_OUT_URV_N

Numeric

A value is required for an analog calibration.

Primary Output UnitsMI_TMCA0000_PRI_OUT_UOM_CCharacter (10)

A value is required. Depending on the value in the Calibration Type field, this field contains one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST
SW 1 Setpoint (Discrete)MI_TMCA0000_SW1_SP_NNumericA value is required for discrete calibration.

Activate Switch 1 (Discrete)

MI_TMCA0000_SPEC_INC_DEC_01_C

NumericA value is required for discrete calibration.
SW 1 Contact StateMI_TMCA0000_SW1_CNTCT_ST_CNumeric

A value is required. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

This field is enabled only when a value exists in the Calibration Strategy field.

Reset Set Point MI_TMCA0000_RESET_SET_POINT_N NumericA value is required for discrete calibration using the GE Druck calibrators.
Ramp Time MI_TMCA0000_RAMP_TIME_N NumericA value is required for discrete calibration using the GE Druck calibrators.
Repeat CountMI_TMCA0000_REP_COUNT_N NumericA value is required for discrete calibration using the GE Druck calibrators.
Calibration Strategy (Single Component)MI_TMCA0000_STRATEGY_CCharacter (25)A value is required for single component analyzer calibration and must match the ID of an existing Calibration Strategy.
Template State MI_TM000000_STATE_CCharacter (50)

This column may only contain one of the System Code IDs in the MI_STATUS System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Loop Power MI_TMCA0000_LOOP_PWR_CCharacter (15)

If using the Fluke calibrator, this column may only contain one of the System Code IDs defined by the FLUKE POWER SOURCE value in the MI_CALIBRATION_REFERENCES System Code Table. If using the GE Druck calibrator, this column may only contain one of the System Code IDs in the MI_CALIBRATION_YES_OR_NO System Code Table.

Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Manual Entered Input Values MI_TMCA0000_IN_MEV_LBooleanEnter True or False.
Manual Entered Output ValuesMI_TMCA0000_OUT_MEV_FLGBooleanEnter True or False.
Performs Square RootMI_TMCA0000_PERF_SQRT_CCharacter (1)

This column may only contain one of the System Code IDs in the MI_YES_NO System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Enable Automated CalibrationsMI_TMCA0000_ENABL_AUTO_CAL_FBooleanEnter True or False.
Custom Input Lower Range ValueMI_TMCA0000_CUST_IN_LRV_NNumericNone
Custom Input Upper Range ValueMI_TMCA0000_CUST_IN_URV_NNumericNone
Custom Output Lower Range ValueMI_TMCA0000_CUST_OUT_LRV_NNumericNone
Custom Output Upper Range ValueMI_TMCA0000_CUST_OUT_URV_NNumericNone
Custom Input Range UOMMI_TMCA0000_CUST_IN_RN_UOM_CCharacter (50)

A value is required. Depending on the value in the Calibration Type field, this field contains one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST
Custom Output Range UOMMI_TMCA0000_CUST_OUT_RN_UOM_CCharacter (50)

A value is required. Depending on the value in the Calibration Type field, this field contains one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST
TC LinearMI_TMCA0000_TC_LIN_FBooleanEnter True or False.
RTD Wiring Configuration MI_TMCA0000_RTD_WIR_CNFG_CCharacter (50)

This column may only contain one of the System Code IDs by the RTD Wiring Configuration value in the MI_CALIBRATION_REFERENCES. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Linear TC LRVMI_TMCA0000_LIN_TC_LRV_NNumericNone
Linear TC URVMI_TMCA0000_LIN_TC_URV_NNumericNone
Custom Output ValuesMI_TMCA0000_CUST_OUT_VAL_FBooleanEnter True or False.
Custom Input ValuesMI_TMCA0000_CUST_IN_VAL_FBooleanEnter True or False.
Temperature Element TypeMI_TMCA0000_TMP_EL_TP_CCharacter (50)

This column may only contain one of the System Code IDs in the MI_CALIBRATION_REFERENCES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Calibration Profile Worksheet

The Calibration Profile worksheet stores the details of the Calibration Profile records.

Field Caption

Field ID

Data Type (Length)

Comments

BATCH_IDBATCH_IDNumeric

A value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.

Profile IDMI_CAL_PROF_PROF_ID_CHRCharacter (255)A value is required and must be unique. This value identifies the Calibration Profile.
Device Type MI_CAL_PROF_DEVI_TYPE_C Character (255)A value is required.
Profile TemplateMI_CAL_PROF_PROF_TEMP_CHRCharacter (50)A value is required.
Calibration Strategy MI_CAL_PROF_CALI_STRA_C Character (50)

A value is required and must match the ID of an existing Calibration Strategy.

Profile Template Family IDMI_CAL_PROF_TEMP_FMLY_ID_CHRCharacter (50)

A value is required. Enter one of the following values based on the calibration type:

Calibration TypeCalibration Family ID
AnalogMI_TMCAAN00
DiscreteMI_TMCADSCT
Single component analyzerMI_TMCASCAN
Multi-component analyzerMI_TMCAMCAN

Analog Template Worksheet

The Analog Template worksheet stores the details of the Calibration Template, Analog records.

Field Caption

Field ID

Data Type (Length)

Comments

BATCH_ID

BATCH_ID

Numeric

A value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.

Template ID

MI_TM000000_ID

Character (255)

A value is required and must be unique. This value identifies the Calibration Template, Analog record. After importing data, the value in this field (in the corresponding record in GE Digital APM) will be updated to include the values in the following fields:

  • Asset ID as configured in the Asset ID Configuration
  • Calibration Type
  • Calibration Strategy
  • Primary Input Range Units
  • Primary Output Range Units

Input Type

MI_TMCA0000_INPUT_TYP_C

Character (50)

A value is required.

This column may only contain one of the System Code IDs in the MI_CALIBRATION_IO_TYPES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Output Type

MI_TMCA0000_OUTPU_TYP_C

Character (50)

This column may only contain one of the System Code IDs in the MI_CALIBRATION_IO_TYPES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Max Error LimitMI_TMCA0000_ERR_LIM_N NumericA value is required.
Primary Input LRVMI_TMCA0000_PRI_IN_LRV_NNumericA value is required.
Primary Input URVMI_TMCA0000_PRI_IN_URV_NNumericA value is required.
Primary Input Range Units

MI_TMCA0000_PRI_IN_RV_UOM_C

Character (10)

A value is required. Depending on the value in the Calibration Type field, this column must contain System Codes in one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST
Primary Output LRV MI_TMCA0000_PRI_OUT_LRV_N

Numeric

A value is required for analog and single component analyzer calibrations.

Primary Output URVMI_TMCA0000_PRI_OUT_URV_N

Numeric

A value is required for analog and single component analyzer calibrations.

Primary Output UnitsMI_TMCA0000_PRI_OUT_UOM_CCharacter (10)

A value is required. Depending on the value in the Calibration Type field, this column must contain System Codes in one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST
Asset IDASSET_IDNumericA value is required. Enter the Asset ID that corresponds to the Asset ID configured in Asset ID Configuration for Equipment, Functional Location, or custom asset that is linked to the Calibration Template. If the value that you enter does not match the Asset ID of any Equipment, Functional Location, or custom asset in the GE Digital APM database, an error message appears, stating that the Asset is not found, and the batch is not imported.
Asset Family IDASSET_FAMILY_IDNumericA value is required. If the Asset corresponds to an Equipment record, then enter MI_EQUIP000. If the Asset corresponds to a Functional Location record, then enter MI_FNCLOC00. If the Asset corresponds to any of the custom asset record, then enter family ID of that asset family.
Profile ID MI_CAL_PROF_PROF_ID_CHRCharacter (255)

A value is required and must be unique. This value identifies the Calibration Profile.

Note: The Profile ID will create a relationship between this Applied Template and the Profile.
Error AssesmentMI_TMCA0000_ERR_ASSES_CCharacter (50)

A value is required.

This column may only contain one of the System Code IDs in the CALIBRATION_ERROR_ASSESSMENT System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Template State MI_TM000000_STATE_CCharacter (50)

This column may only contain one of the System Code IDs in the MI_STATUS System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Loop Power MI_TMCA0000_LOOP_PWR_CCharacter (15)

If using the Fluke calibrator, this column may only contain one of the System Code IDs defined by the FLUKE POWER SOURCE value in the MI_CALIBRATION_REFERENCES System Code Table. If using the GE Druck calibrator, this column may only contain one of the System Code IDs in the MI_CALIBRATION_YES_OR_NO System Code Table.

Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Manual Entered Input ValuesMI_TMCA0000_IN_MEV_LBooleanEnter True or False.
Manual Entered Output ValuesMI_TMCA0000_OUT_MEV_FLGBooleanEnter True or False.
Performs Square RootMI_TMCA0000_PERF_SQRT_CCharacter (1)This column may only contain one of the System Code IDs in the MI_YES_NO System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.
Enable Automated CalibrationsMI_TMCA0000_ENABL_AUTO_CAL_FBooleanEnter True or False.
Custom Input Lower Range ValueMI_TMCA0000_CUST_IN_LRV_NNumericNone
Custom Input Upper Range ValueMI_TMCA0000_CUST_IN_URV_NNumericNone
Custom Output Lower Range ValueMI_TMCA0000_CUST_OUT_LRV_NNumericNone
Custom Output Upper Range ValueMI_TMCA0000_CUST_OUT_URV_NNumericNone
Custom Input Range UOMMI_TMCA0000_CUST_IN_RN_UOM_CCharacter (50)

A value is required. Depending on the calibration type, this column must contain System Codes in one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST
Custom Output Range UOMMI_TMCA0000_CUST_OUT_RN_UOM_CCharacter (50)

A value is required. Depending on the calibration type, this column must contain System Codes in one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST
TC LinearMI_TMCA0000_TC_LIN_FBooleanEnter True or False.
RTD Wiring Configuration MI_TMCA0000_RTD_WIR_CNFG_CCharacter (50)This column may only contain one of the System Code IDs by the RTD Wiring Configuration value in the MI_CALIBRATION_REFERENCES. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.
Linear TC LRVMI_TMCA0000_LIN_TC_LRV_NNumericNone
Linear TC URVMI_TMCA0000_LIN_TC_URV_NNumericNone
Custom Output ValuesMI_TMCA0000_CUST_OUT_VAL_FBooleanEnter True or False.
Custom Input ValuesMI_TMCA0000_CUST_IN_VAL_FBooleanEnter True or False.
Temperature Element TypeMI_TMCA0000_TMP_EL_TP_CCharacter (50) This column may only contain one of the System Code IDs in the MI_CALIBRATION_REFERENCES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Discrete Template Worksheet

The Discrete Template worksheet stores the details of the Calibration Template, Discrete records.

Field Caption

Field ID

Data Type (Length)

Comments

BATCH_ID

BATCH_ID

Numeric

A value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.

Template ID

MI_TM000000_ID

Character (255)

A value is required and must be unique. This value identifies the Template. After importing the data, the value in this field (in the corresponding record in GE Digital APM) will be updated to include the values in the following fields:

  • Asset ID as configured in the Asset ID Configuration
  • Calibration Type
  • Calibration Strategy
  • Primary Input Range Units
Input Type

MI_TMCA0000_INPUT_TYP_C

Character (50)

A value is required.

This column may only contain one of the System Code IDs in the MI_CALIBRATION_IO_TYPES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Output Type

MI_TMCA0000_OUTPU_TYP_C

Character (50)

A value is required.

This column may only contain one of the System Code IDs in the MI_CALIBRATION_IO_TYPES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Max Error LimitMI_TMCA0000_ERR_LIM_N NumericA value is required.
Primary Input LRVMI_TMCA0000_PRI_IN_LRV_NNumericA value is required.
Primary Input URV Primary Input URV Primary Input URV A value is required.
Primary Input Range Units

MI_TMCA0000_PRI_IN_RV_UOM_C

Character (10)

A value is required. Depending on the calibration type, this column must contain a value from one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST
SW 1 Setpoint MI_TMCA0000_SW1_SP_NNumericA value is required.
Activate Switch 1MI_TMCA0000_SPEC_INC_DEC_01_CNumericA value is required.
SW 1 Contact StateMI_TMCA0000_SW1_CNTCT_ST_CNumericA value is required. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.
Reset Set Point MI_TMCA0000_RESET_SET_POINT_N NumericA value is required.
Ramp TimeMI_TMCA0000_RAMP_TIME_N NumericA value is required.
Repeat CountMI_TMCA0000_REP_COUNT_N NumericA value is required.
Asset IDASSET_IDNumericA value is required. Enter the Asset ID that corresponds to the Asset ID configured in Asset ID Configuration for Equipment, Functional Location, or custom asset that is linked to the Calibration Template. If the value that you enter does not match the Asset ID of any Equipment, Functional Location, or custom asset in the GE Digital APM database, an error message appears, stating that the Asset is not found, and the batch is not imported.
Asset Family IDASSET_FAMILY_IDNumericA value is required. If the Asset corresponds to an Equipment record, then enter MI_EQUIP000. If the Asset corresponds to a Functional Location record, then enter MI_FNCLOC00. If the Asset corresponds to any of the custom asset record, then enter family ID of that asset family.
Profile IDMI_CAL_PROF_PROF_ID_CHRCharacter (255)

A value is required and must be unique. This value identifies the Calibration Profile.

Note: The Profile ID will create a relationship between this Applied Template and the Profile.
Template StateMI_TM000000_STATE_CCharacter (50)

This column may only contain one of the System Code IDs in the MI_STATUS System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Loop PowerMI_TMCA0000_LOOP_PWR_CCharacter (15)

If using the Fluke calibrator, this column may only contain one of the System Code IDs defined by the FLUKE POWER SOURCE value in the MI_CALIBRATION_REFERENCES System Code Table. If using the GE Druck calibrator, this column may only contain one of the System Code IDs in the MI_CALIBRATION_YES_OR_NO System Code Table.

Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Manual Entered Input Values MI_TMCA0000_IN_MEV_LBooleanEnter True or False.
Manual Entered Output ValuesMI_TMCA0000_OUT_MEV_FLGBooleanEnter True or False.
Performs Square RootMI_TMCA0000_PERF_SQRT_CCharacter (1)This column may only contain one of the System Code IDs in the MI_YES_NO System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.
Enable Automated CalibrationsMI_TMCA0000_ENABL_AUTO_CAL_FBooleanEnter True or False.
Custom Input Lower Range ValueMI_TMCA0000_CUST_IN_LRV_NNumericNone
Custom Input Upper Range ValueMI_TMCA0000_CUST_IN_URV_NNumericNone
Custom Output Lower Range ValueMI_TMCA0000_CUST_OUT_LRV_NNumericNone
Custom Output Upper Range ValueMI_TMCA0000_CUST_OUT_URV_NNumericNone
Custom Input Range UOMMI_TMCA0000_CUST_IN_RN_UOM_CCharacter (50)

Depending on the calibration type, this column must contain System Codes in one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST
Custom Output Range UOMMI_TMCA0000_CUST_OUT_RN_UOM_CCharacter (50)

A value is required. Depending on the calibration type, this column must contain System Codes in one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST
TC LinearMI_TMCA0000_TC_LIN_FBooleanEnter True or False.
RTD Wiring Configuration MI_TMCA0000_RTD_WIR_CNFG_CCharacter (50)

This column may only contain one of the System Code IDs by the RTD Wiring Configuration value in the MI_CALIBRATION_REFERENCES. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Linear TC LRVMI_TMCA0000_LIN_TC_LRV_NNumericNone
Linear TC URVMI_TMCA0000_LIN_TC_URV_NNumericNone
Custom Output Values MI_TMCA0000_CUST_OUT_VAL_FBooleanEnter True or False.
Custom Input ValuesMI_TMCA0000_CUST_IN_VAL_FBooleanEnter True or False.
Temperature Element TypeMI_TMCA0000_TMP_EL_TP_CCharacter (50)

This column may only contain one of the System Code IDs in the MI_CALIBRATION_REFERENCES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Error AssesmentMI_TMCA0000_ERR_ASSES_CCharacter (50)

A value is required.

This column may only contain one of the System Code IDs in the CALIBRATION_ERROR_ASSESSMENT System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Primary Output UnitsMI_TMCA0000_PRI_OUT_UOM_CCharacter (10)

Depending on the value in the Calibration Type field, this column may contain System Codes in one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST

Single Component Template Worksheet

The Single Component Template worksheet stores the details of the Calibration Template, Single Component Analyzer records.

Field Caption Field ID Data Type (Length) Comments

BATCH_ID

BATCH_ID

Numeric

A value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.

Template IDMI_TM000000_IDCharacter (255)A value is required.
Input TypeMI_TMCA0000_INPUT_TYP_CCharacter (50)

A value is required.

This column may only contain one of the System Code IDs in the MI CALIBRATION IO TYPES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Output TypeMI_TMCA0000_OUTPU_TYP_CCharacter (50)

A value is required.

This column may only contain one of the System Code IDs in the MI CALIBRATION IO TYPES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Calibration StrategyMI_TMCA0000_STRATEGY_CCharacter (25)

A value is required and must match the ID of an existing Calibration Strategy.

Primary Input LRVMI_TMCA0000_PRI_IN_LRV_NNumericA value is required.
Primary Input URVMI_TMCA0000_PRI_IN_URV_NNumericA value is required.
Primary Input Range UnitsMI_TMCA0000_PRI_IN_RV_UOM_CCharacter (50)

A value is required. Depending on the calibration type, this column must contain System Codes in one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST
Primary Output LRVMI_TMCA0000_PRI_OUT_LRV_NNumericA value is required.
Primary Output URVMI_TMCA0000_PRI_OUT_URV_NNumericA value is required.
Primary Output UnitsMI_TMCA0000_PRI_OUT_UOM_CCharacter (50)

A value is required. Depending on the calibration type, this column must contain System Codes in one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST
Calibration TypeMI_TMCA0000_CAL_TYP_CCharacter (50)

A value is required.

This column may only contain one of the System Code IDs in the MI_CALIBRATION_TYPE System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Asset IDASSET_IDNumericA value is required. Enter the Asset ID that corresponds to the Asset ID configured in Asset ID Configuration for Equipment, Functional Location, or custom asset that is linked to the Calibration Template. If the value that you enter does not match the Asset ID of any Equipment, Functional Location, or custom asset in the GE Digital APM database, an error message appears, stating that the Asset is not found, and the batch is not imported.
Asset Family IDASSET_FAMILY_IDNumericA value is required. If the Asset corresponds to an Equipment record, then enter MI_EQUIP000. If the Asset corresponds to a Functional Location record, then enter MI_FNCLOC00. If the Asset corresponds to any of the custom asset record, then enter family ID of that asset family.
Profile IDMI_CAL_PROF_PROF_ID_CHRCharacter (255)

A value is required and must be unique. This value identifies the Calibration Profile.

Note: The Profile ID will create a relationship between this Applied Template and the Profile.
Template Short DescriptionMI_TM000000_SHRT_DSC_CCharacter (255)None
Enterprise <number> CodeMI_TM000000_ERP_01_CD_CCharacter (50)None
Enterprise <number> DescriptionMI_TM000000_ERP_01_DESC_CCharacter (255)None
Template Long DescriptionMI_TM000000_LNG_DSC_TTextNone
Template TypeMI_TM000000_TEMP_TYPE_CCharacter (50)None
Template StateMI_TM000000_STATE_CCharacter (50)

This column may only contain one of the System Code IDs in the MI_STATUS System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Temperature Element TypeMI_TMCA0000_TMP_EL_TP_CCharacter (50)

This column may only contain one of the System Code IDs in the MI_CALIBRATION_REFERENCES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Lock Output RangeMI_TMCA0000_LCK_OUT_RNG_FBooleanEnter True or False.
ManufacturerMI_TMCA0000_MFR_CCharacter (255)None
Model NumberMI_TMCA0000_MOD_NO_CCharacter (255)None
Serial NumberMI_TMCA0000_SN_CCharacter (255)None
Refresh Equipment DataMI_TMCA0000_REF_EQ_DA_FBooleanEnter True or False.
Max Error LimitMI_TMCA0000_ERR_LIM_NNumericNone
Tag DescriptionMI_TMCA0000_TAG_DESCR_CCharacter (255)None
Local IDMI_TMCA0000_LOCAL_ID_NNumericNone
Repeat CountMI_TMCA0000_REP_COUNT_NNumericNone
Reset Set PointMI_TMCA0000_RESET_SET_POINT_NNumericNone
Ramp TimeMI_TMCA0000_RAMP_TIME_NNumericNone
Error AssesmentMI_TMCA0000_ERR_ASSES_CCharacter (50)

A value is required.

This column may only contain one of the System Code IDs in the CALIBRATION_ERROR_ASSESSMENT System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Multi Component Template Worksheet

The Multi Component Template worksheet stores the details of Calibration Template, Multi-Component Analyzer records.

Field Caption

Field ID

Data Type (Length)

Comments

BATCH_ID

BATCH_ID

Numeric

A value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.

Template IDMI_TM000000_IDCharacter (255)A value is required.
Calibration TypeMI_TMCA0000_CAL_TYP_CCharacter (50)A value is required.
Asset IDASSET_IDA value is required. Enter the Asset ID that corresponds to the Asset ID configured in Asset ID Configuration for Equipment, Functional Location, or custom asset that is linked to the Calibration Template. If the value that you enter does not match the Asset ID of any Equipment, Functional Location, or custom asset in the GE Digital APM database, an error message appears, stating that the Asset is not found, and the batch is not imported.
Asset Family IDASSET_FAMILY_IDNumericA value is required.
Profile IDMI_CAL_PROF_PROF_ID_CHRCharacter (255)

A value is required and must be unique. This value identifies the Calibration Profile.

Note: The Profile ID will create a relationship between this Applied Template and the Profile.
Template Short DescriptionMI_TM000000_SHRT_DSC_CCharacter (255)None
Enterprise <number> CodeMI_TM000000_ERP_01_CD_CCharacter (50)None
Enterprise <number> DescriptionMI_TM000000_ERP_01_DESC_CCharacter (255)None
Template TypeMI_TM000000_TEMP_TYPE_CCharacter (50)None
Template Long DescriptionMI_TM000000_LNG_DSC_TTextNone
Template StateMI_TM000000_STATE_CCharacter (50)

This column may only contain one of the System Code IDs in the MI_STATUS System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Temperature Element TypeMI_TMCA0000_TMP_EL_TP_CCharacter (50)

This column may only contain one of the System Code IDs in the MI_CALIBRATION_REFERENCES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Lock Output RangeMI_TMCA0000_LCK_OUT_RNG_FBooleanEnter True or False.
Input TypeMI_TMCA0000_INPUT_TYP_CCharacter (50)

This column may only contain one of the System Code IDs in the MI_CALIBRATION_IO_TYPES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

ManufacturerMI_TMCA0000_MFR_CCharacter (255)None
Model NumberMI_TMCA0000_MOD_NO_CCharacter (255)None
Max Error LimitMI_TMCA0000_ERR_LIM_NNumericNone
Serial NumberMI_TMCA0000_SN_CCharacter (255)None
Refresh Equipment DataMI_TMCA0000_REF_EQ_DA_FBooleanEnter True or False.
Tag DescriptionMI_TMCA0000_TAG_DESCR_CCharacter (255)None
Local IDMI_TMCA0000_LOCAL_ID_NNumericNone
Repeat CountMI_TMCA0000_REP_COUNT_NNumericNone
Reset Set PointMI_TMCA0000_RESET_SET_POINT_NNumericNone
Ramp TimeMI_TMCA0000_RAMP_TIME_NNumericNone

Single Comp Temp Detail Worksheet

The Single Comp Temp Detail worksheet is used to define Calibration Template Detail, Analyzer records for a Calibration Template, Single Component Analyzer record.

Field Caption Field ID Data Type (Length) Comments
BATCH_ID

BATCH_ID

Numeric

A value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.

Template Parent IDPARENT_IDCharacter (255)A value is required and must match the ID of a Calibration Template, Single Component Analyzer. Otherwise, all the rows in the batch are skipped.
Calibration Template Detail IDMI_TD000000_IDCharacter (100)If you do not enter a value in this column, after you import data, the corresponding field is populated with a system-generated value.
Component NameMI_TDCAAN00_CMPNT_NM_CCharacter (255)

This column may only contain one of the System Code IDs in the MI CHEMICAL COMPONENTS System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Component ValueMI_TDCAAN00_CMPNT_VAL_NNumericNone
Component UnitsMI_TDCAAN00_CMPNT_UOM_CCharacter (50)

This column may only contain one of the System Code IDs defined by the STANDARD GAS UOM value in the MI_CALIBRATION_REFERENCES System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Standard Balance ContentMI_TDCAAN00_BLNC_CNTNT_FBooleanEnter True or False.
Percent of Scale Test PointMI_TDCAAN00_PCT_SCL_NNumericNone
Percent of Scale Sequence NumberMI_TDCAAN00_PCT_SQNC_NNumericNone
Input Up/DnMI_TDCAAN00_UP_DN_TP_CCharacter (50)None
Calibration Template Detail DescriptionMI_TD000000_SHRT_DESC_CCharacter (255)None

Calibration Task Worksheet

The Calibration Task worksheet stores the details of the Calibration Task records.

Field Caption

Field ID

Data Type (Length)

Comments

BATCH_ID

BATCH_ID

Numeric

A value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.

Task ID

MI_TASK_ID

Character (255)

A value is required.

Asset ID

ASSET_ID

Character (255)A value is required. Enter the Asset ID that corresponds to the Asset ID configured in the Asset ID Configuration for Equipment, Functional Location, or custom asset field that is linked to the Calibration Template. If the value that you enter does not match the Asset ID of any Equipment, Functional Location, or custom asset in the GE Digital APM database, an error message appears, stating that the Asset is not found, and the batch is not imported.
Asset Family IDASSET_FAMILY_IDNumericA value is required. If the Asset corresponds to an Equipment record, then enter MI_EQUIP000. If the Asset corresponds to a Functional Location record, then enter MI_FNCLOC00. If the Asset corresponds to any of the custom asset record, then enter family ID of that asset family.

Task Assigned To

MI_TASK_ASSGN_TO_C

Character (50)

None

Task Description

MI_TASK_DESC_TX

Character

None

Task State

MI_TASK_TASK_STATE_CHR

Character (50)

This column may only contain one of the System Code IDs in the CTST System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Reoccurring

MI_TASK_REOCC_FLG

Boolean

Enter True or False.

Route Number

MI_TASK_ROUTE_NO_C

Character (25)

None

Unconstrain Min/Max Dates

MI_TASK_UNCONSTR_MN_MX_DT_FLG

Boolean

Enter True or False.

Last Date

MI_TASK_LAST_DATE_DT

Date

Enter a value in the following format: YYYY-MM-DD HH:mm:ss

Rejectable

MI_TASK_REJEC_FLG

Boolean

Enter True or False.

Modifiable

MI_TASK_MODIF_FLG

Boolean

Enter True or False.

Task Type

MI_TASK_TASK_TYPE_CHR

Character (50)

None

Min Interval

MI_TASK_MIN_INTER_NBR

Numeric

None

Desired Interval

MI_TASK_DESIR_INTER_NBR

Numeric

None

Desired Interval UOM

MI_TASK_DESIR_INTER_UOM_C

Character (50)

This column may only contain one of the System Code IDs in the MI_STRATEGY_REFERENCE System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Max Interval

MI_TASK_MAX_INTER_NBR

Numeric

None

Calibration Template ID

MI_TASKCALB_CALIB_TEMPL_ID_N

Numeric

A value is required and must match the ID of a Calibration Template. If it does not match, the Calibration Task will still be created, but not linked to a Calibration Template.

Calibration Event Worksheet

The Calibration Event worksheet stores details of the following records:

  • Calibration, Analog
  • Calibration, Discrete
  • Calibration, Analyzer Single Component
  • Calibration, Analyzer Multi-Component

Field Caption

Field ID

Data Type (Length)

Comments

BATCH_ID

BATCH_ID

Numeric

A value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.

Event ID

MI_EVENT_ID

Character (255)

A value is required.

Calibration Strategy

MI_EVCALIBR_STRATEGY_C

Character (20)

A value is required and must match the ID of an existing Calibration Strategy.

Calibration TypeMI_EVCALIBR_CALIB_TYP_CCharacter (50)

This column may only contain one of the System Code IDs in the MI_CALIBRATION_TYPE System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Primary Output LRV

MI_EVCALIBR_PRI_OUT_LRV_N

Numeric

A value is required.

Primary Input LRV

MI_EVCALIBR_PRI_IN_LRV_N

Numeric

A value is required.

Calibration Error Limit

MI_EVCALIBR_ERR_LIM_N

Numeric

A value is required.

Primary Output URV

MI_EVCALIBR_PRI_OUT_URV_N

Numeric

A value is required.

Primary Input URV

MI_EVCALIBR_PRI_IN_URV_N

Numeric

A value is required.

Asset IDASSET_IDNumericA value is required. Enter the Asset ID that corresponds to the Asset ID configured in Asset ID Configuration for Equipment, Functional Location, or custom asset that is linked to the Calibration Template. If the value that you enter does not match the Asset ID of any Equipment, Functional Location, or custom asset in the GE Digital APM database, an error message appears, stating that the Asset is not found, and the batch is not imported.
Event Family IDFamily_IDCharacter

A value is required. Depending on the calibration type, this column must contain one of the following values:

Calibration TypeValue
AnalogMI_EVCAANLG
DiscreteMI_EVCADSCT
Single Component AnalyzerMI_EVCAANSC
Multi-Component AnalyzerMI_EVCAANMC

Primary Output Units

MI_EVCALIBR_PRI_OUT_UOM_C

Character (10)

A value is required. Depending on the calibration type, this column must contain System Codes from one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST
Primary Input Range Units MI_EVCALIBR_PRI_IN_RV_UOM_CCharacter (10)

A value is required. Depending on the calibration type, this column must contain a value from one of the following System Code Tables:

Calibration TypeSystem Code Table
Fluke 74XUOME
Druck DPI620 (Genii)CALIBRATION_DRUCK_UOM_LIST
Druck DPI61xCALIBRATION_DRUCK_UOM_LIST
CMXCALIBRATION_CMX_UOM_LIST
Event Start DateMI_EVENT_STRT_DTDateA value is required. Enter a value in the following format: YYYY-MM-DD HH:mm:ss
Calibration Template Key MI_EVCALIBR_CAL_TMP_KEY_NNumericA value is required. This column may only contain a value that exists in the list in the Template ID field for Calibration Templates.
Asset Family IDASSET_FAMILY_IDNumericA value is required. If the Asset corresponds to an Equipment record, then enter MI_EQUIP000. If the Asset corresponds to a Functional Location record, then enter MI_FNCLOC00. If the Asset corresponds to any of the custom asset record, then enter family ID of that asset family.
Input Characteristic Curve MI_EVCALIBR_IN_CC_CURV_CCharacter (25)

This column may only contain one of the System Code IDs in the MI CHARACTERISTIC CURVE System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Calibration Closed MI_EVCALIBR_CAL_CLOSE_LBooleanEnter True or False.

Location ID

MI_EVENT_LOC_ID_CHR

Character (255)

None

Equipment Manufacturer

MI_EVCALIBR_ASST_MFG_C

Character (255)

None

Equipment Model Number

MI_EVCALIBR_ASST_MOD_NO_C

Character (255)

None

Equipment Serial Number

MI_EVCALIBR_ASST_SN_C

Character (255)

None

Maintenance Type

MI_EVCALIBR_MAINT_TYPE_C

Character (25)

This column may only contain one of the System Code IDs in the MI_MAINTENANCE_TYPE System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

WO Reference (Event)

MI_EVCALIBR_WO_NO_C

Character (30)

None

Scheduled Calibration Date

MI_EVCALIBR_SCHED_CAL_D

Date

Enter a value in the following format: YYYY-MM-DD HH:mm:ss

Calibration Technician

MI_EVCALIBR_TECH_NM_C

Character (35)

None

Calibration Approval By

MI_EVCALIBR_CAL_APPR_NM_C

Character (50)

None

Secondary Output LRVMI_EVCALIBR_SEC_OUT_LRV_NNumericNone
Secondary Output UnitsMI_EVCALIBR_SEC_OUT_UOM_CCharacter (10)None
Secondary Output URVMI_EVCALIBR_SEC_OUT_URV_NNumericNone
Test Equipment ID No 1MI_EVCALIBR_TST_EQU_ID_01_CCharacter (255)The value in this column must match the ID of a Test Equipment.
Test Equipment ID No 2MI_EVCALIBR_TST_EQU_ID_02_CCharacter (255)The value in this column must match the ID of a Test Equipment.
Test Equipment ID No 3MI_EVCALIBR_TST_EQU_ID_03_CCharacter (255)The value in this column must match the ID of a Test Equipment.
Test Equipment Manufacturer 1MI_EVCALIBR_TST_EQU_MFR_01_CCharacter (50)None
Test Equipment Manufacturer 2MI_EVCALIBR_TST_EQU_MFR_02_CCharacter (50)None
Test Equipment Manufacturer 3MI_EVCALIBR_TST_EQU_MFR_03_CCharacter (50)None
Test Equipment Model Number 1MI_EVCALIBR_TST_EQU_MDL_01_CCharacter (50)None
Test Equipment Model Number 2MI_EVCALIBR_TST_EQU_MDL_02_CCharacter (50)None
Test Equipment Model Number 3MI_EVCALIBR_TST_EQU_MDL_03_CCharacter (50)None
Test Equipment Serial Number 1MI_EVCALIBR_TST_EQU_SN_01_CCharacter (50)None
Test Equipment Serial Number 2MI_EVCALIBR_TST_EQU_SN_02_CCharacter (50)None
Test Equipment Serial Number 3MI_EVCALIBR_TST_EQU_SN_03_CCharacter (50)None
Test Equipment Cal. Expire 1MI_EVCALIBR_TST_EQ_CAL_EX_1_DDateEnter a value in the following format: YYYY-MM-DD HH:mm:ss
Test Equipment Cal. Expire 2MI_EVCALIBR_TST_EQ_CAL_EX_2_DDateEnter a value in the following format: YYYY-MM-DD HH:mm:ss
Test Equipment Cal. Expire 3MI_EVCALIBR_TST_EQ_CAL_EX_3_DDateEnter a value in the following format: YYYY-MM-DD HH:mm:ss
Test Equipment Last Cal. 1MI_EVCALIBR_TST_EQ_LS_CAL_1_DDateEnter a value in the following format: YYYY-MM-DD HH:mm:ss
Test Equipment Last Cal. 2MI_EVCALIBR_TST_EQ_LS_CAL_2_DDateEnter a value in the following format: YYYY-MM-DD HH:mm:ss
Test Equipment Last Cal. 3MI_EVCALIBR_TST_EQ_LS_CAL_3_DDateEnter a value in the following format: YYYY-MM-DD HH:mm:ss
Location Short DescriptionMI_EVENT_LOC_SHRT_DESC_CHRCharacter (255)None
Asset TypeMI_EVENT_ASST_TYP_CHRCharacter (50)None
Asset Short DescriptionMI_EVENT_ASST_DESC_CHRCharacter (255)None
Asset CategoryMI_EVENT_ASST_CTGRY_CHRCharacter (50)None
Secondary Input LRVMI_EVCALIBR_SEC_IN_LRV_NNumericNone
Secondary Input Range UnitsMI_EVCALIBR_SEC_IN_RV_UOM_CCharacter (10)None
Secondary Input URVMI_EVCALIBR_SEC_IN_URV_NNumericNone
Event End DateMI_EVENT_END_DTDateEnter a value in the following format: YYYY-MM-DD HH:mm:ss
Event Long DescriptionMI_EVENT_LNG_DSC_TXCharacterNone
Actual Work TimeMI_EVENT_ACTUAL_WRK_TM_NNumericNone
Off Line DurationMI_EVCALIBR_OFF_LINE_DURA_NNumericNone
Calibration Task IDMI_EVCALIBR_CAL_TSK_ID_CCharacter (50)

This column may contain a value that exists in the list in the Task ID field for Calibration Task records. If the value that you enter does not match the Task ID of any Calibration Task in the GE Digital APM database, then this field is blank after you import data.

Test Equipment Status 1MI_EVCALIBR_TST_EQU_STAT_01_CCharacter (50)None
Test Equipment Status 2MI_EVCALIBR_TST_EQU_STAT_02_CCharacter (50)None
Test Equipment Status 3MI_EVCALIBR_TST_EQU_STAT_03_CCharacter (50)None
Output Characteristic CurveMI_EVCALIBR_OUT_CC_CURV_CCharacter (25)

This column may only contain one of the System Code IDs in the MI CHARACTERISTIC CURVE System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Calibration Result Worksheet

The Calibration Result worksheet stores details of the following records:

  • Calibration Results, Analog
  • Calibration Result, Discrete
  • Calibration Results, Analyzer

Field Caption

Field ID

Data Type (Length)

Comments

BATCH_ID

BATCH_ID

Numeric

A value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.

As Found Error

MI_CALRESLT_AFE_N

Numeric

A value is required.

Input Measure AF

MI_CALRESLT_IN_MEAS_AF_N

Numeric

A value is required.

Primary Output AF

MI_CALRESLT_PRI_OUT_AF_N

Numeric

A value is required.

Calibration Sequence Number

MI_CALRESLT_TST_SEQ_N

Number

A value is required.

Standard NameMI_CRANZR00_CMPNT_NM_CCharacter (255)

A value is required for multi-component analyzer calibration.

This column may only contain one of the System Code IDs in the MI_CHEMICAL_COMPONENTS System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Event ID

MI_CALRESLT_ID

Character (255)

A value is required. Enter the ID of one of the following records:

  • Calibration Results, Analog
  • Calibration Result, Discrete
  • Calibration Results, Analyzer

Percent of Scale TP

MI_CALRESLT_POS_TP_N

Numeric

A value is required.

Input Up/Dn

MI_CALRESLT_UP_DN_TP_C

Character (2)

A value is required. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Switch Number (Discrete)MI_CRDS0000_SW_NNumericA value is required for discrete calibration.
As Found Reset Point (Discrete)MI_CRDS0000_AF_RSET_NNumericA value is required for discrete calibration.
As Found Trip PointMI_CRDS0000_AF_TP_NNumericA value is required for discrete calibration.
As Found Dead BandMI_CRDS0000_AF_DB_NNumericA value is required for discrete calibration.
As Left Reset PointMI_CRDS0000_AL_RSET_NNumericA value is required for discrete calibration.
As Left Trip PointMI_CRDS0000_AL_TP_NNumericA value is required for discrete calibration.
As Left Dead BandMI_CRDS0000_AL_DB_NNumericA value is required for discrete calibration.
Standard ValueMI_CRANZR00_CMPNT_VAL_NNumericA value is required for single component and multi-component analyzer calibrations.
Calibration Results Family IDFamily_IDCharacter (255)

A value is required. Depending on the family of the Calibration Results record, enter one of the following IDs:

Calibration Results FamilyID
Calibration Results, AnalogMI_CRAN0000
Calibration Result, DiscreteMI_CRDS0000
Calibration Results, AnalyzerMI_CRANZR00
As Found ValueMI_CRANZR00_AF_VAL_NNumericA value is required for multi-component analyzer calibrations.

Primary Output AL

MI_CALRESLT_PRI_OUT_AL_N

Numeric

None

Input Measure AL

MI_CALRESLT_IN_MEAS_AL_N

Numeric

None

Parent Key(Single/Multi Component)MI_CRANZR00_PARE_KEY_NNumericA value is required for single component or multi-component analyzer calibrations. This column may only contain a value that exists in the list in the Event ID field for Calibration, Single Component Analyzer or Calibration, Multi-Component Analyzer records.

Parent Key (Analog)

MI_CRAN0000_PARE_KEY_N

Numeric

A value is required for analog calibrations. This column may only contain a value that exists in the list in the Event ID field for Calibration, Analog records.

Parent Key (Discrete)

MI_CRDS0000_PARE_KEY_N

Numeric

A value is required for discrete calibrations. This column may only contain a value that exists in the list in the Event ID field for Calibration, Discrete records.

Calibration Recommendation Worksheet

The Calibration Recommendation worksheet stores details of the Calibration Recommendation records.

Field Caption

Field ID

Data Type (Length)

Comments

BATCH_ID

BATCH_ID

Numeric

A value is required and must match one of the values that you enter in the Batch worksheet. Additionally, all the records that are linked to one another must contain the same batch number.

Target Completion Date

MI_REC_TARGE_COMPL_DATE_DT

Date

A value is required. Enter a value in the following format: YYYY-MM-DD HH:mm:ss

Recommendation ID

MI_REC_ID

Character (255)

A value is required and must be unique. This value identifies the Recommendation.

Asset IDASSET_IDNumericA value is required. Enter the Asset ID that corresponds to the Asset ID configured in Asset ID Configuration for Equipment, Functional Location, or custom asset that is linked to the Calibration Template. If the value that you enter does not match the Asset ID of any Equipment, Functional Location, or custom asset in the GE Digital APM database, an error message appears, stating that the Asset is not found, and the batch is not imported.
Calibration Type

MI_RECCLBN_CALEVNT_CAT_CHR

Character (100)

A value is required.

Event ID

Event ID

Character

None

Asset Family IDASSET_FAMILY_IDNumericA value is required. If the Asset corresponds to an Equipment record, then enter MI_EQUIP000. If the Asset corresponds to a Functional Location record, then enter MI_FNCLOC00. If the Asset corresponds to any of the custom asset record, then enter family ID of that asset family.

Reevaluate?

MI_REC_REEVAL_FLG

Boolean

Enter True or False.

Calibration Recommendation Basis

MI_RECCLBN_CALEVNT_ID_CHR

Character (100)

Enter the Event ID.

Reevaluation Notification List

MI_REC_REEVAL_NOTIF_LIST_CHR

Character (2000)

None

Days Before Due Date to be Notified

MI_REC_DAYS_BEF_DUE_DT_NOT_NBR

Numeric

None

Generate Work Request

MI_REC_WO_INTERFACE_FLAG_F

Boolean

Enter True or False.

Meridium Task ID

MI_REC_MERIDIUM_TASK_ID_C

Character (255)

None

Final State Lock

MI_REC_FINAL_STATE_LOCK_F

Boolean

Enter True or False.

Final Approver Name

MI_REC_FINAL_APPROVE_NAME_C

Character (255)

None

Required Equipment Status

MI_REC_REQUI_EQUIP_STATU_CHR

Character (50)

This column may only contain one of the System Code IDs in the MI_STATUS System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Reevaluation Alert Body Text

MI_REC_REEVAL_EMAIL_TX

Character

None

Implementation Alert Text

MI_REC_NOTIF_EMAIL_TEXT_CHR

Character

None

Alert Assignee When Due?

MI_REC_NOTIFY_RP_FLG

Boolean

Enter True or False.

Reevaluation Date

MI_REC_REEVAL_DT

Date

Enter a value in the following format: YYYY-MM-DD HH:mm:ss

Business Impact

MI_REC_IMPAC_CHR

Character (100)

This column may only contain one of the System Code IDs in the MI_BUSINESS_IMPACT System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Frequency of Alert After Due Date

MI_REC_NOTIF_AFTER_DD_CHR

Character (50)

This column may only contain one of the System Code IDs in the MI_FREQ_OF_ALERTS System Code Table. Refer to the (Picklist) worksheet in the data loader workbook for a list of values that you can enter in this column.

Completion CommentsMI_REC_CLOSE_COMME_TXCharacterNone
Implemented DateMI_REC_COMPL_DATE_DTDateEnter the value in the following format: YYYY-MM-DD HH:mm:ss
Recommendation HeadlineMI_REC_SHORT_DESCR_CHRCharacter (255)None
Recommendation DescriptionMI_REC_LONG_DESCR_TXCharacterNone
Recommendation PriorityMI_REC_PRIORITY_CCharacter (50)None
Author LockMI_REC_AUTHOR_LOCK_FBooleanEnter True or False.
Assigned To NameMI_REC_ASSIG_NM_CHRCharacter (255)None
Mandatory DateMI_REC_MANDA_DATE_DTDateEnter a value in the following format: YYYY-MM-DD HH:mm:ss
Create SAP Notification? MI_REC_CREATE_SAP_NOTIF_FLGBooleanEnter True or False.
Work Request ReferenceMI_REC_WK_REQ_REF_CHRCharacter (50)None
Work Request EquipmentMI_REC_WR_EQUIP_CCharacter (255)None
Work Request Functional LocationMI_REC_WR_LOC_CCharacter (255)None
Technical NumberMI_REC_TECHNICAL_NUM_CCharacter (50)None
StatusMI_REC_STATU_CHRCharacter (255)None
Recommendation TypeMI_REC_TYPE_CHRCharacter (255)None
Reviewer NameMI_REC_REVIE_NM_CHRCharacter (255)None
Author NameMI_REC_AUTHO_NM_CHRCharacter (255)None
Creation Date MI_REC_CREAT_DATE_DTDateEnter a value in the following format: YYYY-MM-DD HH:mm:ss
MI_SM_STATE_ID_CMI_SM_STATE_ID_CCharacterNone
MI_SM_STATE_ENTERED_DMI_SM_STATE_ENTERED_DDateEnter a value in the following format: YYYY-MM-DD HH:mm:ss
MI_SM_STATE_OWNER_ID_CMI_SM_STATE_OWNER_ID_CCharacterNone

About the Calibration Data Loader Load Verification

About This Task

Following a successful data load, the user is able to navigate to any of the imported templates, to view the details and logic tree associated with the template, and to import template content into an analysis.

Procedure

  1. Access the details of the import job. These details indicate if any errors were encountered during the data load. The log may help account for any records that are not loaded.
  2. In Calibration Management or Record Manager, access the assets specified in the data loader workbook, and then verify that the expected Calibration records are present or updated, and that any associated records that you expected to be created are also present in the database.
  3. To access a list of Calibration Templates created after a specific date, run the following query: SELECT [MI_TMCA0000].[MI_TM000000_ID] "Template ID", [MI_TMCA0000].[MI_TMCA0000_CAL_TYP_C] "Calibration Type", [MI_TMCA0000].[MI_TMCA0000_INPUT_TYP_C] "Input Type", [MI_TMCA0000].[MI_TMCA0000_OUTPU_TYP_C] "Output Type", [MI_TMCA0000].[MI_TMCA0000_IS_MAST_TEMP_L] "Is Master Template", [MI_TMCA0000].LAST_UPDT_DT "Created Date"FROM [MI_TMCA0000] WHERE [MI_TMCA0000].LAST_UPDT_DT >= (? :d :caption='Enter Date')
  4. To access a list of Calibration Tasks created after a specific date, run the following query: SELECT [MI_TASKCALB].[MI_TASK_ID] "Task ID", [MI_TASKCALB].[MI_TASK_LAST_DATE_DT] "Last Date", [MI_TASKCALB].[MI_TASK_NEXT_DATE_DT] "Next Date", [MI_TASKCALB].[MI_TASK_DESIR_INTER_NBR] "Desired Interval", [MI_TASKCALB].[MI_TASK_DESIR_INTER_UOM_C] "Desired Interval UOM", [MI_TASKCALB].LAST_UPDT_DT "Created Date" FROM [MI_TASKCALB] WHERE [MI_TASKCALB].LAST_UPDT_DT >= (? :d :caption='Enter Date')
  5. To access a list of Calibrations created after a specific date, run the following query: SELECT [MI_EVCALIBR].[MI_EVENT_ID] "Event ID", [MI_EVCALIBR].[MI_EVCALIBR_CALIB_TYP_C] "Calibration Type", [MI_EVCALIBR].[MI_EVCALIBR_STRATEGY_C] "Calibration Strategy", [MI_EVCALIBR].[MI_EVCALIBR_CAL_CLOSE_L] "Calibration Closed", [MI_EVCALIBR].[MI_SM_STATE_ID_C] "Calibration State", [MI_EVCALIBR].LAST_UPDT_DT "Created Date"FROM [MI_EVCALIBR] WHERE [MI_EVCALIBR].LAST_UPDT_DT >= (? :d :caption='Enter Date')