Fixed Defects in iFIX 6.5
Defect# | Area | Description |
---|---|---|
735091 | WorkSpace | Startup Profile Manager cannot list domain members when connecting to domains with 15 characters. This issue is resolved in iFIX 6.5. |
740156 | Database Manager | Dbcvt.exe crashes when upgrading databases from iFIX 5.8 that contain SQD blocks.This issue is resolved in iFIX 6.5. |
816875 | Database Manager | DBCVT does not copy the Event Messaging in Suspend Mode option on DA tags when upgrading a 5.8 PDB to a 6.1 PDB. This issue is resolved in iFIX 6.5. |
801088, 00816459, 851489 | Database Manager | Database exporter crashes due to buffer overrun. This issue is resolved in iFIX 6.5. |
771064 | WorkSpace | Alarm column format is incorrect in iFIX 6.0 after upgrade from iFIX 5.8. This issue is resolved in iFIX 6.5. |
776856 | WorkSpace | On Picture with 'SmoothShapes' property is set to True, Arc control disappears when AngleUnits property is set to '1-Radians'. This issue is resolved in iFIX 6.5. |
815345 | Alarming OPCUA | Event message from pre-6.0 SCADA is missing tagname, alarm type and current value fields. This issue is resolved in iFIX 6.5. |
670604 | Database Manager | Polish characters cannot be entered directly into Description cell of spreadsheet in the DatabaseManager using Polish Programmers keyboard. This issue is resolved in iFIX 6.5. |
732675 | Database Manager | Database Manager stops responding after aborting tag copying/pasting process. This issue is resolved in iFIX 6.5. |
733107 | Database Manager | Database Manager does not sort on tagname correctly. This issue is resolved in iFIX 6.5. |
769442 | Alarming | Alarm filtering fails with more than nine conditions. This issue is resolved in iFIX 6.5. |
794970 | Database Manager | CSV Import with block type missing for a tag causes a DataBaseManager Crash. This issue is resolved in iFIX 6.5. |
539040 | WorkSpace | Cannot change Local Logical Name in SCU without administrative privileges. This issue is resolved in iFIX 6.5. |
750613, 00844926 | WorkSpace | Application Validator fails to open FactoryGlobals.fxg when WorkSpace is running. This issue is resolved in iFIX 6.5. |
792510 | WorkSpace | WorkSpace goes into an endless feedback loop and crashes when evaluating animation expressions containing cross referenced local variables. This issue is resolved in iFIX 6.5. |
803926, 00807749, 898880 | WorkSpace | Long tag name support causes VisiconXData.ocx to fail when ordering by the A_TAG field. This issue is resolved in iFIX 6.5. |
659885 | WorkSpace | Animations using shared lookup tables are exported into JSON file incorrectly. This issue is resolved in iFIX 6.5. |
687594, 845664, 845667 | WorkSpace | ALT+F4 key combination does not close WorkSpace in Run mode. This issue is resolved in iFIX 6.5. |
790083, 641208 | WorkSpace | Login window stays open for several minutes after successful login. This issue is resolved in iFIX 6.5. |
790083 | WorkSpace | Password expiration warning is not shown on the correct day. This issue is resolved in iFIX 6.5. |
799781 | WorkSpace | BackupRestore application in silent mode displays message dialog box. This issue is resolved in iFIX 6.5. |
764778 | WorkSpace | When iFIX is running as a service, the Windows Taskbar shows when the auto logged in iFIX user does not have task switching rights. This issue is resolved in iFIX 6.5. |
670519 | WorkSpace | FixDataSystem may randomly fail to read or write to known good tags. This issue is resolved in iFIX 6.5. |
620125 | WorkSpace | With old coordinate picture, difference in zoom level on copy and paste operations makes copied control very small or very large. This issue is resolved in iFIX 6.5. |
753324 | WorkSpace | WorkSpace crashes when picture with description string over 259 characters exists in PIC folder. This issue is resolved in iFIX 6.5. |
679211 | WorkSpace | GetSignature method has no way to require operator to enter a perform comment in Electronic Signature dialog. This issue is resolved in iFIX 6.5. |
679424 | WorkSpace | OPC20iFix crashes when clients try to exceed 32767 tags per group. This issue is resolved in iFIX 6.5. |
682363 | WorkSpace | "While fetching Alarm from AlarmUserQ the method call ""eda_alm_get_user_que_item"" of EDA Toolkit crashes the WorkSpace."" This issue is resolved in iFIX 6.5. |
741734 | WorkSpace | iFIX STARTUP.log truncates at 50 lines. This issue is resolved in iFIX 6.5. |
826171 | Recipe | Recipe upload and verification fail when a tag's A_DESC field is used in a recipe item. This issue is resolved in iFIX 6.5. |
840054, 805263, 863978 | WorkSpace | WSQLODC.exe crashes due to internal buffer overflow. This issue is resolved in iFIX 6.5. |
843990 | Alarming | Alarm Summary message color not updated after changing the tag's alarm priority. This issue is resolved in iFIX 6.5. |
00839500, 00833428, 850372 | WorkSpace | Cannot use Totalizer block F_CV field and cannot configure D16 block. This issue is resolved in iFIX 6.5. |
609084 | WorkSpace | WorkSpace doesn't follow ""AlwaysShowMaximized"" preference set in WorkSpace.ini. This issue is resolved in iFIX 6.5. |
657268, 871735 | WorkSpace | Enhanced Line Chart displays NODATA for data sources that rarely change value when the data sources are added/deleted/modified at runtime. The NODATA condition doesn't self correct until either the data changes or another modification is made. This issue is resolved in iFIX 6.5. |
663006 | WorkSpace | SCU crash when accessing the Alarm Area Database from a secondary SCADA after being changed on the primary node. This issue is resolved in iFIX 6.5. |
00521131_CS0089534 | WorkSpace | When multiple Dynamos exist on picture, double-click on Dynamo sometimes incorrectly runs Edit Dynamo Script for another object. This issue is resolved in iFIX 6.5. |
802772 | WorkSpace | Add ability to export security configuration programmatically. This issue is resolved in iFIX 6.5. |
850297, 851613, 850297 | WorkSpace | Invalid Command Line Parameter error when running Security Configurator from the SCU. This issue is resolved in iFIX 6.5. |
620131 | WorkSpace | Added feature to revert repeated Arrow key operation in single undo command. This issue is resolved in iFIX 6.5. |
427939 | WorkSpace | Historian tag containing hyphen in the last block fails to add to Chart Group with the error ""Expressions containing Historical items is not allowed"". This issue is resolved in iFIX 6.5. |
754136 | SAC | TcpTask may crash when using SQT block. This issue is resolved in iFIX 6.5. |
768994 | WorkSpace | With iFIX59_WorkSpace_013 installed, picture with Title Bar opening a little too far to the right in Run Mode. This issue is resolved in iFIX 6.5. |
768998 | WorkSpace | WorkSpace Menu Bar, Status Bar and Scroll Bar are cut off once user comes back to Configuration Mode from Full Screen in Run Mode. This issue is resolved in iFIX 6.5. |
720829, 805258, 822380 | WorkSpace | WorkSpace Title bar visible in run mode after reconnecting to RDP session. This issue is resolved in iFIX 6.5. |
765020, 739944 | WorkSpace | A thick border displays when WorkSpace runs in Full Screen mode on system with Aero theme. This issue is resolved in iFIX 6.5. |
783539, 788889, 844214 | WorkSpace | Some pictures created before iFIX59_WorkSpace_13 SIM show scroll bars or are scaled differently when opened with iFIX59_WorkSpace_13 SIM. This issue is resolved in iFIX 6.5. installed |
647434 | WorkSpace | Animations in a picture with Title Bar stop updating while an user holds the Left Mouse Button down on Title Bar during Run Mode. This issue is resolved in iFIX 6.5. |
862622 | WorkSpace | WorkSpace crash when Windows full user name exceeds 31 characters. This issue is resolved in iFIX 6.5. |
725211 | WorkSpace | Change Windows Password functionality of Security Login allows password with maximum length of 20 characters but stores only 19 characters. This issue is resolved in iFIX 6.5. |
744127 | Historian | WorkSpace takes a long time to start due to large list of Historian servers. This issue is resolved in iFIX 6.5. |
842691 | OPC AE Server | Subscription with filter by area does not receive alarm from tag whose alarm area configuration has been changed. This issue is resolved in iFIX 6.5. |
610631 | Networking | When 200 View nodes are connected to a SCADA node, the last View node name configured using NSD tag is shown blank on the WorkSpace. This issue is resolved in iFIX 6.5. |
726426 | Networking | TcpTask crashes. This issue is resolved in iFIX 6.5. |
872556 | OPC AE Server | iFix OPC AE Server does not log the name of the user that acknowledged an alarm. This issue is resolved in iFIX 6.5. |
00846436, 00874597 | WorkSpace | Corrupt picture leads to WorkSpace memory leak. This issue is resolved in iFIX 6.5. |
844282, 866337, 868886, 869820, 862418 | WorkSpace | WorkSpace hangs and displays ""Network Transaction"" when viewing tag status. This issue is resolved in iFIX 6.5. |
864757, 868039 | WorkSpace | WorkSpace cannot write to an OPC Data Server point. This issue is resolved in iFIX 6.5. |
817661, 853651, 00877807 | WorkSpace | Enhanced Chart reverts to default color settings after picture is closed. This issue is resolved in iFIX 6.5. |
824263 | WorkSpace | When Standard chart control is placed in rightmost or bottommost area of picture, chart's Zoom-In and Time Cursor functions do not work. This issue is resolved in iFIX 6.5. |
00819447, 00817975, 00880851, 866416 | WorkSpace | Conmgr.exe shutdown at startup, or crashes due to memory leak. This issue is resolved in iFIX 6.5. |
00783758, 00824672 | WorkSpace | Some of the SCU dialogs and Standard Chart dialogs are cut off for some languages. This issue is resolved in iFIX 6.5. |
829325 | WorkSpace | When script for mouse move event is added for an OLE object control, Tooltip blinks when mouse hovers on control. This issue is resolved in iFIX 6.5. |
838206 | WorkSpace | VisiconX Grid Control, with 'DisplayHeaders' property set to False, makes header visible when switch to run mode. This issue is resolved in iFIX 6.5. |
866136 | SAC | Analog Alarm (AA) tag alarm is not fully regenerated after quickly disabling and then re-enabling alarming. This issue is resolved in iFIX 6.5. |
868607 | WorkSpace | MS Forms controls are resized incorrectly when visibility is false. This issue is resolved in iFIX 6.5. |
829231 | WorkSpace | iFIX Standard Chart AddLegendItem VBA call may fail. This issue is resolved in iFIX 6.5. |
846288 | WorkSpace | When Rectangle is set with Fill Style 'GradientFillStyle' and Fade Type 'Reflected', the proportion of color blending varies with ratio of control's height and width. This issue is resolved in iFIX 6.5. |
878390 | WorkSpace | For Tags of 'AA' and 'DA' Block types, 'A_ENAB' field is listed twice in 'Field Names' list of Expression Builder. This issue is resolved in iFIX 6.5. |
879556 | WorkSpace | Export Picture utility gives error due to lost functions. This issue is resolved in iFIX 6.5. |
00864617, 00871309, 00882856 , 00889112, 00889635, 00889766 | Security | Automatic Login credentials are blank or corrupted when configured from a remote node. This issue is resolved in iFIX 6.5. |
00864617, 00871309, 00882856 , 00889112, 00889635, 00889766 , 00879018 | Security | Automatic Login when using mixed iFIX versions and a shared security path. This issue is resolved in iFIX 6.5. |
885606 | Database Manager | Export of large process database is incomplete. This issue is resolved in iFIX 6.5. |
871969 | Historian | ihFIXCtl.exe cannot stop and start the second instance of the Historian FIX Collector. This issue is resolved in iFIX 6.5. |
851542 | WorkSpace | Alarm horn get silenced even when process of alarm acknowledgment with Electronic Signature is aborted. This issue is resolved in iFIX 6.5. |
00862443, 00861296, 00889826 | WorkSpace | On Picture initialization in run mode, Animation output doesn't get set if the source value remains unchanged. This issue is resolved in iFIX 6.5. |
888373 | WorkSpace | Historian iFIX Collector does not run as a service when started with iFIX. This issue is resolved in iFIX 6.5. |