CIMPLICITY Statistical Process Control
Project
|
Purpose
|
To reduce the number of milliseconds CimView will wait to connect to an SPC database (for an inserted SPC ActiveX control) before the wait times out.
|
Comment
|
SQL Express 2005 and higher require a user name and password to connect to the database. If SPC has not been configured with the correct user name and password and one or a group of CimView screens includes an SPC Control CimView will appear to be hanging for the default time (60 seconds) while trying to connect.
Do either of the following.
- Enter the correct credentials in the SPC Document Properties dialog box.
- Use SPC_DB_CONNECT_TIMEOUT to reduce the wait time.
|
Value
|
Number (of milliseconds)
|
|
Minimum
|
250 ms
|
|
Maximum
|
60000 ms
|
Default Value
|
60000
|
|